Signallers

LTT2 Expander

Product code: PW-128-A-X

The LTT2 Expander for the Control Unit of the Sigma Control L (SCL) type.

See full description
Functionalities:
Certificates:
Product description
Technical details

The LTT2 Expander for the Control Unit of the Sigma Control L (SCL) type. Use of the LTT2 Expander enables connection of up to 10 visual and audio warning devices of the LTT2 type controlled from voltage outputs.

Two types of the expander are available:

  • PW-128-A-230 – for the power voltage of 230 VAC
  • PW-128-A-24 – for the power voltage 24 V DC
Power supply
  • Voltage Vcc

PW-128-A-230: 230 V ~ ± 10%
PW-128-A-24: 21 – 29 V , 3 A

  • Power

PW-128-A-230 – 60 W

Environment
  • Ambient temperatures

-10 – +50 °C

  • Humidity

10 – 90% long term,
without condensation

IP

IP54

Protection class
  • Power supply 230 V
  • Power supply 24 V
  • II
  • III

Cross-section of wires for
clamping terminals

0.2 – 2.5 mm2
(use sleeves
2 x 1 mm2 or 2 x 0.75 mm2
for twin conductors)

Cable glands
(cable diameter range)

5 – 10 mm

Materiał obudowy

ABS

Sposób montażu

4 screw holes 4 mm,
hole spacing 235mm x 160 mm

Videos

Placement and role in the system

Files to download
Datasheets:
LTT2 warning devices to expander to SCL - Datasheet
Download file
CE declarations:
LTT2 Warning devices expander to SCL - Declaration of Conformity
Download file
Skip to content
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.