Gas Detectors

Alpa EcoWent XT

Product code: PW-097-CO

Alpa EcoWent XT Gas Detector is an advanced and versatile device designed for detection of carbon monoxide concentration in public access facilities, such as underground garages and car parks.

See full description
Functionalities:
Certificates:
Product description
Technical details
Supported gases

Alpa EcoWent XT Gas Detector is an advanced and versatile device designed for detection of carbon monoxide concentration in public access facilities, such as underground garages and car parks. Presence of the hazardous gas is revealed by means of a electrochemical sensor, which guarantees reliable operation of the device without false alarms and, in consequence, smooth operation of the Gas Safety System deployed on the monitored facilities.

The detectors are immune to humidity, variations of ambient temperature and presence of other gases. The device measures concentration of gas within established time intervals and information about exceeding of permissible thresholds it provided to the system operator when the LED indicator provided on the side of the device is on.

The communication between the detector and the master Control Unit is provided by the 4-20 mA output signal.

The Alpa EcoWent XT Gas Detector is not designed for installation in areas with potentially explosive atmospheres.

Power voltage
  • VCC

10 – 42 V

  • ICC

40 mA

Environment
  • Ambient temperatures

-20 – 50 °C

0 – 50 °C ( storage )

  • Humidity

10 – 90% long term

30 – 90% long term ( storage )

0 – 99% short term

  • Pressure

1013 ± 10% hPa

Detected substance

Carbon monoxide (CO)

Measuring range

0 – 300 ppm

Standard configuration
  • warning 1

20 ppm

  • warning 2

40 ppm

  • alarm

100 ppm

IP

IP43

Digital input parameters

RIN

200 Ω

Analogue input parameters

RLOAD_MAX

200 Ω

The output signal according to the operating status of the detector
  • Failure

<0.1 mA

  • Operation

4 mA

  • Warning 1

9 mA

  • Warning 2

11 mA

  • Alarm

15 mA

Integrated signalling equipment
(optical)

LED controls

Protection class

III

Cable glands (cable diameter range)

Cable glands pressed into installation
pipes – pipe diameter 16 mm
Multi-range cable glands – cable
diameter 3.5 – 12 mm

Acceptable cables

0.25 – 1.5 mm2 – solid wire
0.25 – 1 mm2 – stranded wire

Enclosure material

ABS

Weight

0.3 kg

Mandatory periodic inspection

Every 12 months

( Validity of the calibration certificate )

Mounting

4 holes for screws with the diameters
of 4 mm

Placement and role in the system

Files to download
Datasheets:
Alpa EcoWent XT Gas Detector - Datasheet
Download file
Users's manual:
Alpa EcoWent XT Gas Detector - User Manual
Download file
CE declarations:
Alpa EcoWent XT Gas Detector - Declaration of Conformity
Download file
Skip to content
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.