Gas Detectors

Teta EcoDet

Product code: PW-106-LPG

Teta EcoDet gas detector are monitoring devices designed to check propane-butane (C3H8, C4H10) concentration in open-access confined spaces (e.g. boiler rooms, manufacturing or warehouse shops heated with gas-fired IR radiators).

See full description
Functionalities:
Certificates:
Product description
Technical details
Supported gases

Teta EcoDet gas detector are monitoring devices designed to check propane-butane (C3H8, C4H10) concentration in open-access confined spaces (e.g. boiler rooms, manufacturing or warehouse shops heated with gas-fired IR radiators) and meant as components of the innovative Teta Gas Safety System. The device performs cyc­lical measurements of gas concentration in the air, then the information on correct operation or exceeding the set thresholds is transmitted to the user by controls flashing on the detector. Communication between the detector and the compatible Control Unit takes place through power supply and signalling bus Teta Bus. The system is designed as installer-friendly – it allows any order of wires during connection of power supply and data bus.

 

Key advantages of detector:

  • Unique addressing​ – The Teta Gas System offers easy and clear assignment and verification of addresses associated with every single Teta EcoDet detector. The Control Unit provides information about each individual detector separately for every single device.
  • Two-wired bus – Both power voltage and data signals are transmitted via a single and commonly available two-wired cable, e.g. of YDY type – no twisted-pair lines, shielding screens, etc.
  • Catalytic sensors – Catalytic sensors applied to measure concentration of Hazardous Gases guarantee reliable control for ventilation systems and alarms that warn about possibility of fires or explosions. The sensors are insensitive to moisture, temperature variations or presence of other gases.
Power supply
  • Voltage VCC

12 – 50 V

  • Power

1.5 W

Environment

• Ambient temperatures

-20 – 50 °C / 20 – 50 °C ( storage )

• Humidity

10 – 90% long term

30 – 90% long term ( storage )

0 – 99% short term

• Pressure

1013 ± 10% hPa

Measure substance

LPG (C3H8, C4H10)

Measure range

0 – 50% LEL

IP

IP43

Digital communication parameters

• Communication port

Teta BUS

Integrated signalling equipment (visual)

LED indicators
7-segment type display LED

Protection class

III

Cable glands (cable diameter
range)

Gland pressed into the installation
pipe –

diameter of the pipe 16 mm.

Glands multiband – diameter of wire
3.5 – 12 mm

Acceptable cables

0.2 – 2.5 mm2– solid wire
0.2 – 2.5 mm2– multi-wire cable

Enclosure

ABS

Weight

0.3 kg

Mandatory periodic inspection

Every 12 months

( Validity of the calibration certificate )

Mounting

4 screw holes 4 mm, spacing as shown
in the picture

Videos

Placement and role in the system

Files to download
Datasheets:
Teta EcoDet Gas Detector - Datasheet
Download file
Users's manual:
Teta EcoDet Gas Detector - User Manual
Download file
CE declarations:
Teta EcoDet Gas Detector - Declaration of Conformity
Download file
Skip to content
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.