Gas Detectors

Teta EcoN

Product code: PW-111-NO2

Teta EcoN gas detector is monitoring devices designed to check nitrogen dioxide concentrations in open-access confined spaces (garages and underground car parks).

See full description
Functionalities:
Certificates:
Product description
Technical details
Supported gases

Teta EcoN is an addressable Gas Detector for sensing nitrogen dioxide (NO2) concentrations, designed as part of Teta Gas Safety System. The device performs cyc­lical measurements of gas concentration in the air, then the information on correct operation or exceeding the set thresholds is transmitted to the user by controls flashing on the detector. Communication between the detector and the compatible Control Unit takes place through power supply and signalling bus Teta BUS. The system is designed as installer-friendly – it allows any order of wires during connection of power supply and data bus.

 

Key advantages of detector:

  • power supply and data transmission via a single, two – wired cable,
  • insensitive to polarization of the connection,
  • simple and clear method for scanning and identification of detector addresses,
  • simple identification of the detector status,
  • 3 alarm thresholds,
  • built-in electrochemical sensor insensitive to changes of ambient conditions.
Power supply
  • Voltage VCC

12 – 50 V

  • Power CO/NO2
  • Power CO+LPG

0,5 W

1.5 W

Environment

• Ambient temperatures

-20 – 50 °C / 0 – 50 °C ( storage )

• Humidity

10 – 90% long term

30 – 90% long term ( storage )

0 – 99% short term

• Pressure

1013 ± 10% hPa

Measure substance

Carbon monoxide (CO)

Nitrogen dioxide (NO2)

Measure range

Carbon monoxide (CO) 0 – 300 ppm

Nitrogen dioxide (NO2) 0 – 10 ppm

IP

IP43

Digital communication parameters

Communication port

Teta BUS

Integrated signalling equipment (visual)

LED indicators
7-segment type display LED

Protection class

III

Cable glands (cable diameter
range)

Gland pressed into the installation pipe
diameter of the pipe 16 mm.

Glands multiband

diameter of wire 3.5 – 12 mm

Acceptable cables

0.2 – 2.5 mm2– solid wire
0.2 – 2.5 mm2– multi-wire cable

Enclosure

ABS

Weight

0,3 kg

Mandatory periodic inspection

Every 12 months

( Validity of the calibration certificate )

Mounting

4 screw holes 4 mm, spacing as shown in
the picture

Videos

Placement and role in the system

Files to download
Datasheets:
Teta EcoN Gas Detector - Datasheet
Download file
Users's manual:
Teta EcoN Gas Detector - User Manual
Download file
CE declarations:
Teta EcoN Gas Detector - Declaration of Conformity
Download file
Skip to content
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.