Control Unit Modules

Teta MOD Control 1

Product code: PW-0108

Teta MOD Control 1 is responsible for communication with Teta Gas detectors, processing field signals, indication of the system status for the operator as well as overall control of the system operation.

See full description
Functionalities:
Certificates:
Product description
Technical details

Control Unit Module Teta MOD Control 1 is a device designed as a part of the Gas Safety Systems Teta Gas. The module uses the Digital Data Transmission – Teta Bus to enable both power supply and addressable communication with field gas detectors by means of merely a single pair of wires. Teta MOD Control 1 is responsible for communication with Teta gas detectors, processing field signals, indication of the system status for the operator as well as overall control of the system operation.

 

Key advantages of the module:

  • Handling up to 50 devices connected directly to the Teta Bus port:
    • handling up to 50 gas detectors,
    • handling up to 8 valve controllers,
    • handling up to 26 signalling devices (optical-acoustic signalling devices or warning LED display).
  • 6 relay outputs
  • 2 binary inputs.
  • Identification of hazardous locations – in case of gas leaks on the facility area the control unit enables operators to identify locations with possible hazards.
  • Broad configuration options with the following functionalities:
    • discrimination of signals from detectors of flammable gases or toxic gases – it enables separation of signals from various sources of gas hazards and selective control of the ventilation system. It is also possible to produce a signal to trip the fire protection system only in selected cases, when it is actually needed,
    • control of actuators by signals from a group of detectors installed on a specific area (e.g. in one room or workshop).
  • Separate control outputs for flammable and toxic gases to be monitored.

 

Device configuration:

 

Product Code Device Description
PW-108A Teta MOD Control 1 Control Unit Module Teta MOD Control 1 Control Unit Module for DIN rail mounting.
PW-086-Control1-S Teta MOD Control 1-S Control Unit Module Moduł Jednostki Sterującej Teta MOD Control 1 enclosed in a distribution box, for wall mounting, IP65.
Supports 24V DC UPS.
Dimensions 432/290.5/160
PW-086-Control1-S24 Teta MOD Control 1-S24 Control Unit Module Teta MOD Control 1 Control Unit Module with 230/24V 60W power supply, enclosed in a distribution box, for wall mounting, IP65.
Dimensions 432 x 290.5 x 160
PW-086-Control1-S48-60 Teta MOD Control 1-S48-60 Control Unit Module Teta MOD Control 1 Control Unit Module with 230/48V 60W power supply, enclosed in a distribution box, for wall mounting, IP65.
Dimensions 432 x 290.5 x 160
PW-086-Control1-S48-100 Teta MOD Control 1-S48-100 Control Unit Module Teta MOD Control 1 Control Unit Module with 230/48V 100W power supply, enclosed in a distribution box, for wall mounting, IP65.
Dimensions 432 x 290.5 x 160
PW-086-Control1-S48-150 Teta MOD Control 1-S48-150 Control Unit Module Teta MOD Control 1 Control Unit Module with 230/48V 150W power supply, enclosed in a distribution box, for wall mounting, IP65.
Dimensions 432 x 290.5 x 160
PW-086-Control1-S-UP300 Teta MOD Control 1-S-UP300 Control Unit Module Teta MOD Control 1 Control Unit Module with 24/48V 300W power supply, enclosed in a distribution box, for wall mounting, IP65.

Supports 24V DC UPS.
Dimensions 295 x 458 x 129

 

Power supply
  • Voltage VCC

15 – 50 V

  • Power PCC

2.5 W

Environment
  • Ambient temperatures

0 – 50 °C

  • Humidity

10 – 90% long term
0 – 99% short term

  • Pressure

1013 ± 10% hPa

  • pH

5.5 – 7

IP

IP20

Digital input parameters (binar, DI)
  • RIN

10 kΩ

  • Inactive (not negated)

0 – 1 V

  • Active (not negated)

10 – 50 V

  • Other

Signal type: DC (any polarisation),

AC (50 Hz), Any polarization > 1s

Digital output parameters
  • Relay

Floating contacts, NO/NC

AC12: 230 V ~ / 3 A
DC1: 230 V / 0.25 A
DC1: 24 V / 3 A
Not protected against overloading

Digital communication parameters
  • TETA BUS port
    • Communication protocol

Teta Bus

  • GTW port
    • Electric standard

RS – 485

    • Communication protocol

Modbus ASCII / RTU, 4800 – 115200 b/s,

no parity / even parity/ odd parity,

number of bits 7/8 (only for Modbus ASCII)

Integrated signalling equipment
(visual)

LCD alphanumerical display 2 x 16
LED indicator

Integrated signalling equipment
(audible)

70 dB 1 m distance

Protection class

III

Cable glands (cable diameter range)

0.08 – 2.5 mm2 (cable lugs 2 x 1 mm2 or 2 x 0.75 mm2

should be used for double wires)

Enclosure material

Self-extinguishing PPO

Weight

0.4 kg

Mounting

On DIN-35 / TS35

Videos

Placement and role in the system

Files to download
Datasheets:
Teta MOD Control 1 Control Unit Module - Datasheet
Download file
Users's manual:
Teta MOD Control 1 Control Unit Module - User Manual
Download file
CE declarations:
Teta MOD Control 1 Control Unit Module - Declaration of Conformity
Download file
Others:
System Guidebook - Gas Detection & Safety System Teta Gas
Download file
System Configuration Table
Download file
Skip to content
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.